Flowserve 400MD Logix Manual de usuario

Busca en linea o descarga Manual de usuario para Hardware Flowserve 400MD Logix. Flowserve 400MD Logix User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 106
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
USER INSTRUCTIONS
Installation &
Reference Guide
Logix 3400MD
Digital Positioner
FCD LGENIM3405-02 11/13
Vista de pagina 0
1 2 3 4 5 6 ... 105 106

Indice de contenidos

Pagina 1 - USER INSTRUCTIONS

USER INSTRUCTIONSInstallation &Reference GuideLogix 3400MD Digital PositionerFCD LGENIM3405-02 11/13

Pagina 2

1 Logix 3400MD Digital Positioner Description1.1 IntroductionThis section is intended for users who have never worked with the Logix 3400MD digital p

Pagina 3 - Contents

10.17 Logix 3400MD Fault StatesThe following procedure describes hot to setup the fault states in the Logix 3400MD:• In the Resource block verify th

Pagina 4

10.19 Logix 3400MD Digital Input (DI) OperationThe DI(LO) is a discrete that is set when the actual position of the actuator is equal or less than th

Pagina 5 - Introduction

List of FiguresFigure 1.1 Fieldbus Positioner (Logix 3400MD Digital Positioner) 10Figure 1.2 Functional Block Diagram of Logix 3400MD Digital Posit

Pagina 6

List of TablesTable 2.1 Components Required for Logix 3400MD Digital Positioner Installation 14Table 2.2 Installation / Operation Task Summary 15Tab

Pagina 7 - Definitions

Table 8.25 Virtual Field Device (VFD) List Objects 68Table 8.26 Control Parameters Table 70Table 8.27 Unit Parameters Table 71Table 8.28 Diagnostic

Pagina 8 - Technical Assistance

Logix 3400MD Digital Positioner LGENIM3405-02 11/13105

Pagina 9

Flowserve Headquarters5215 N. O’Connor Blvd.Suite 2300Irving, TX 75039Phone: +1 972 443 6500Flowserve CorporationFlow Control1350 N. Mt. Springs Parkw

Pagina 10 - 1.1 Introduction

Figure 1.2 Functional Block Diagram of Logix 3400MD Digital Positioner Operating with other InstrumentsTheory of OperationFigure 1.3 Logix 3400MD Digi

Pagina 11 - Percentage

• Soft limits or MPC functions are disabled• Valve has zero deviation with a present input command of 50 percent• Actuator is tubed air-to-openGive

Pagina 12 - 1.3 Fieldbus Overview

ApplicationAn application is software that contains function block data and operating parameters (objects) which help define the operation of a device

Pagina 13 - 2.2 Installation Components

Table 2.1 Components Required for Logix 3400MD Digital Positioner InstallationComponents DescriptionLogix3400MDDigitalPositioner Fieldbus positioner.P

Pagina 14 - Operator Interface

Table 2.2 Installation / Operation Task SummaryTask Procedure Refer to . . .- Bench Check (optional) (Bench configuration) Section 3, Bench Configurat

Pagina 15 - 3.2 Bench Check

Figure 3.1 Connecting wiring device.4. At the junction block, connect a fieldbus terminator in parallel with the device.5. Connect a power supply , pow

Pagina 16 - 4.1 Introduction

4.2 Considerations for Logix 3400MD Digital PositionerEvaluate ConditionsThe Logix 3400MD digital positioner is designed to operate in common indoor

Pagina 17 - Evaluate Conditions

Temperature LimitsTable 4.1 lists the operating temperature limits for Logix 3400MD digital positioner.Table 4.1 Operating Temperature LimitsAmbient T

Pagina 18 - 5.2 Mounting Variations

Figure 5.1 Typical Linear Actuator-mounted Installation Figure 5.2 Rotary Transfer Case MountingFigure 5.3 Rotary Valve with Four-bar LinkageLogix 340

Pagina 20 - Fieldbus Device Profile Type

Figure 5.4 Logix 3400MD Digital Positioner Mounted to a Diaphragm Actuator5.3 Wiring Logix 3400MD Digital PositionerWiring the Logix 3400MD Digital P

Pagina 21 - For reference purposes

Inside the electronics housing of the Logix 3400MD digital positioner is the terminal block for connecting external wiring as shown in Figure 5.5. Tab

Pagina 22

2. Feed fieldbus cable through one of conduit entrances on either side of electronics housing. Plug whichever entrance not used. CAUTION: The Logix 340

Pagina 23 - 6.1 Introduction

Answer: FF specifies a 10-32V operation range. A fieldbus compatible power supply with terminators should be used. NOTE: The Logix 3400MD is driven from

Pagina 24 - 6.4 Device Configuration

CAUTION Before proceeding with the tasks in this section the Logix 3400MD digital positioner must be installed and wired correctly. The user should b

Pagina 25 - Device Configuration Example

Fieldbus Configuration ApplicationThe Logix 3400MD digital positioner is configured using a fieldbus configuration application running on a operator stati

Pagina 26 - Dip Switch

LAS CapabilityThe Logix 3400MD digital positioner is capable of operating as the Link Active Scheduler (LAS). The LAS is a fieldbus device which contro

Pagina 27 - 6.6 Simulation Dip Switch

Table 6.1 Write Protect dip Switch SettingsTo Set the Dip Switch to:Enable read and write access to the device’s configuration. (Factory-set default)O

Pagina 28 - 6.9 Configuration Tasks

6.8 Making Initial ChecksIdentifying the Logix 3400 Digital PositionerBefore proceeding, verify the following to make sure that the user is communica

Pagina 29 - 8 Configuration Description

10 Write configuration to the fieldbus network.The configuration changes are sent to the appropriate fieldbus devices on the network.11 Save the device co

Pagina 30 - 8.3 Block Description

ContentsIntroduction 51 Logix 3400MD Digital Positioner Description 101.1 Introduction 101.2 Fieldbus Logix 3400MD Digital Positioner 101.3 Fiel

Pagina 31 - Block Descriptions

The key elements of the FBAP are:• Logix block objects and their parameters (and consist of the following block types)• Resource block• Transducer

Pagina 32 - 8.4 Resource Block

Table 8.1 Function Block Application Process ElementsBlock Type FunctionResourceContains data which describes the hardware (physical) characteristics

Pagina 33

Table 8.2 Block Parameter List Column DescriptionColumn Name DescriptionIndexA number that corresponds to the sequence of the parameter in the block p

Pagina 34 - 8.5 Main Transducer Block

Index Origin Name Store Date Type Default Value10 STND MANUFAC_ID SR Simple UNSIGNED32 RES_VAL_MANUFAC_ID11 STND DEV_TYPE SR Simple UNSIGNED16 RES_VAL

Pagina 35

DL_APPSTATEDL_SIZEDL_CHECKSUMREVISION_ARRAYA read-only parameter that contains the application firmware revision level for:FB Board Software Revision:

Pagina 36 - Transducer Block Diagram

26 MFG CALIBRATION_STATUS R Simple BIT_STRING 027 MFG MAIN_RESERVED_1 NRW Simple FLOATING_POINT 028 MFG P_GAIN SRW Simple FLOATING_POINT 229 MFG I_GAI

Pagina 37 - Parameter Definitions

78 MFG LEAK_CLASS NRW Simple UNSIGNED8 9979 MFG VALVE_FLAGS NRW Simple UNSIGNED8 9980 MFG VALVE_TRIMMAT NRW Simple UNSIGNED8 9981 MFG VALVE_TRIMCHAR N

Pagina 38

Figure 8.2 Transducer Block DiagramTransducer Block Valtek Product-defined ParametersTable 8.6 describes the Logix parameters included in the transduce

Pagina 39 - 8.6 Tech Transducer Block

FINAL_VALUE_CUTOFF_LO: If FINAL_VALUE is less than FINAL_VALUE_CUTOFF_LO the positioner will saturate the actuator in a closed posi-tion. There is a

Pagina 40

Signatures See Section 10.13, Initiating a Valve Signature for more details on using the signature acquisition functions of the Logix 3400MD digital p

Pagina 41

8.13 PID Function Block 508.14 Link Objects 548.15 View Objects 558.16 Alert Objects 618.17 Alarm and Event Reporting 628.18 Trend Objects

Pagina 42 - 8.7 MD Transducer Block

Index Origin Name Store Date Type Default Value37MFG D_GAIN_EFFECTIVE R Simple UNSIGNED16 038MFG D_GAIN_FILTER SRW Simple UNSIGNED16 039MFG PRESS_CTRL

Pagina 43

Index Origin Name Store Date Type Default Value88MFG SIG_DATA1 R Array INTEGER16 All 089MFG SIG_DATA2 R Array INTEGER16 All 090MFG SIG_DATA3 R Array I

Pagina 44 - AO Block Connections

• Calibration Auto: allows the user to specify the auto calibration (default) or to enter into a job calibration mode.LX_SPI_STATUS_FLAGS Should a lo

Pagina 45 - AO Block Parameter List

Index Origin Name Store Date Type Default Value26 MFG PST_TIME_TO_TARGET NR Simple FLOATING_POINT 027 MFG PST_RESULT R Simple UNSIGNED8 028 MFG PST_TI

Pagina 46 - AO Block Diagram

Index Origin Name Store Date Type Default Value78 MFG FRICTION_LOW_PERCENT_YELLOW NR Simple FLOATING_POINT 079 MFG PRESSURE_DIFFERENTIAL R Simple FLOA

Pagina 47 - DO Block Description

The OUT parameter of the AO block is used to set the FINAL_POSITION_VALUE in the transducer block, as modified by the FINAL_VALUE_RANGE.READBACK_OUT tr

Pagina 48 - IS Block Description

AO Block DiagramFigure 8.3 is a block diagram showing the key components of the AO function block.Figure 8.3 AO Function Block DiagramClearing Block C

Pagina 49 - OS Block Description

NOTE: SIMULATE.ENABLE can only be set TRUE when the Simulate dip switch is in the “On” position when the device is powered up or a pro-cessor restart

Pagina 50 - 8.13 PID Function Block

The functionality of these parameters follows the standard Fieldbus definitions as defined in the Foundation Fieldbus specifications.8.10 Digital Input

Pagina 51

Table 8.12 IS Function Block Parameter ListIndex Origin Name Store Date Type Default Value0 STND INPUT_SELECTOR SRW Record BLOCK 01 STND ST_REV SR Sim

Pagina 52 - PID Block Diagram

IntroductionCopyright, Notices and TrademarksWhile this information is presented in good faith and believed to be accurate, Flowserve disclaims the im

Pagina 53 - PID Tuning Parameters

Index Origin Name Store Date Type Default Value8 STND OUT_1 RWO Record FLOAT_S 0x1C;0.09 STND OUT_2 RWO Record FLOAT_S 0x1C;0.010 STND OUT_1_RANGE SRW

Pagina 54 - 8.15 View Objects

Index Origin Name Size Date Type Default Value23 STND GAIN 4 Simple FLOATING_POINT 124 STND RESET 4 Simple FLOATING_POINT FLT_MAX25 STND BAL_TIME 4 Si

Pagina 55

Index Origin Name Size Date Type Default Value73 MFG FUTURE1 4 Simple FLOATING_POINT 074 MFG PID_BLOCK_TEST 8 Array UNSIGNED8 0,0,0,0,0,0,0,0Table 8.1

Pagina 56

PID Block DescriptionPID control function block is an algorithm that produces an output signal in response to the measured variable and the set-point.

Pagina 57

8.14 Link ObjectsThe function blocks configured to control a process are linked, or connected by objects within the devices. These links allow the use

Pagina 58

Logix 3400MD Digital Positioner View ObjectsIn the Logix 3400MD digital positioner, four view objects have been defined for each of the blocks. All st

Pagina 59

31 MAX_NOTIFY 132 LIM_NOTIFY 133 CONFIRM_TIME 434 WRITE_LOCK 135 UPDATE_EVT36 BLOCK_ALM37 ALARM_SUM 8 838 ACK_OPTION 239 WRITE_PRI 140 WRITE_ALMManufa

Pagina 60

28 P_GAIN SRW 4  4       29 I_GAIN SRW 2  2       30 D_GAIN

Pagina 61 - 8.16 Alert Objects

83 VALVE_TRIMNO NRW 1      1   84 VALVE_SN NRW 32     32    85 STEM_DIAM

Pagina 62 - 3400MD Status Alarms

13 GRANT_DENY 214 IO_OPTS 215 STATUS_OPTS 216 READBACK 5 517 CAS_IN 5 518 SP_RATE_DN 419 SP_RATE_UP 420 SP_HI_LIM 421 SP_LO_LIM 422 CHANNEL 223 FSTATE

Pagina 63

AWG American Wire GaugeDB DatabaseDD Device DescriptionDDL Device Description LanguageDI Digital InputDO Digital OutputEEPROM Electrically Erasa

Pagina 64 - Travel Accumulator

21 SP_HI_LIM 422 SP_LO_LIM 423 GAIN 424 RESET 425 BAL_TIME 426 RATE 427 BKCAL_IN 528 OUT_HI_LIM 429 OUT_LO_LIM 430 BKCAL_HYS 431 BKCAL_OUT 532 RCAS_IN

Pagina 65 - 8.20 Device Description

63 LO_LO_ALM64 DV_HI_ALM65 DV_LO_ALMManufacturer Specific Parameters66 PID_FORM 167 ALGO_TYPE 168 OUT_LAG 469 GAIN_NLIN 470 GAIN_COMP 4 471 ERROR_ABS 4

Pagina 66 - 8.22 System Management

Fieldbus Alarm MessagesAlarm messages are usually transparent to the user. A host system typically receives these messages and presents them to the us

Pagina 67 - Sync and Scheduling Objects

Function BlockParameter 3400 Alert/AlarmItems GREYED OUT are factor default masked off (NOT ACTIVE)Defined BitsXD_MAIN_BLOCK_ERRBLINK_CODELED BlinkMAIN

Pagina 68 - Address Assignment Objects

Pressure AlarmsPressure alarms are only available on models with advanced diagnostics (Logix 3400MD digital positioner). Advanced diagnostic models a

Pagina 69 - 8.23 Network Management

So, 1.2 inches is added to the travel accumulator. New dead band thresholds of 100 percent (80 percent present position plus 20 percent dead band) and

Pagina 70 - CONTROL PARAMETERS

• Methods Wizard to help configure and commission the positionerStandard and Device-specific DDStandard DD descriptions for function blocks and transdu

Pagina 71 - Unit Parameters

8 Identify (manager) no9 Locating function blocks (manager) no10 FMS server role yes11 Application clock synch (timeslave) yes12 Scheduling function b

Pagina 72 - Informational Parameters

TIME_LAST_RCVDPRIMARY_AP_TIME_PUBLISHERThe application clock time contained in the last clock message.The node address of the primary time publisher f

Pagina 73

Object Description OD Index Default ValueVERSION_OF_SCHEDULE The version number of the function block schedule. 275 0FBScheduleEntry#1 Default setting

Pagina 74

DefinitionsTerm Abbrev. DefininitionAlarmThe detection of a block leaving a particular state and when it returns back to that state.ApplicationA softwar

Pagina 75

Unsupported ServicesThe following is a list of services which are not supported (not used) in the Logix 3400MD digital positioner FBAP:• FB_Action (a

Pagina 76

Parameter Name Bit or Byte Values DescriptionXD_FSTATE_OPT No Bit 0x00Bit 1 0x01Bit 2 0x02Fail to Last Known Set PointFail Valve ClosedFail Valve Open

Pagina 77 - 9 Calibration

Diagnostic ParametersTable 8.28 Diagnostics Parameters TableParameter Name Bit or Byte Values DescriptionDIAGNOSTIC_LEVEL 023StandardAdvancedProPST_RE

Pagina 78 - 9.3 Calibration

Parameter Name Bit or Byte Values DescriptionVALVE_CLASS 01234567891011121314151617181920212223990.25 inch / DN 60.5 inch / DN 150.75 inch / DN 201.0

Pagina 79 - Canceling Calibration

Parameter Name Bit or Byte Values DescriptionVALVE_PACKTYPE 0123499Single Packing PTFESingle Packing GraphiteDouble Packing PTFEDouble Packing Graphit

Pagina 80 - 10 Troubleshooting

Parameter Name Bit or Byte Values DescriptionVALVE_TRIMNO 01234567891011121314151617181920212223242526990.10 - 0.12 in (2.5 - 3.0 mm)0.13 - 0.15 in (3

Pagina 81 - 10.3 Device Troubleshooting

Parameter Name Bit or Byte Values DescriptionACT_SIZE 202122232425262729303132333435363738394041424344454647484950515253545556575859606163646566676869

Pagina 82 - Non-functioning Blocks

Parameter Name Bit or Byte Values DescriptionACT_SIZE 8687888990919293949596979899100101102103105Fisher 657-46Fisher 657-50Fisher 657-60Fisher 657-70F

Pagina 83 - 10.4 Device Diagnostics

CAUTION: The configurator application can be used to perform the calibration procedures. The software application is not a calibrated measurement sour

Pagina 84 - Configuration Errors

11 Auto Tune Positioner Only active when Re-Cal is done12 JogCal - Waiting for user to set pointInitiates the monitoring of the button for five secon

Pagina 85

ReferencesPublications from the Fieldbus FoundationFlowserve recommends that the user obtain these publications, which provide additional information

Pagina 86

10 Troubleshooting10.1 IntroductionThis section contains information about identifying device faults and suggested actions to correct them. The approa

Pagina 87 - 10.8 Simulation Mode

10.3 Device TroubleshootingDevice Not Visible on NetworkIf the device is not seen on the fieldbus network, the device may not be powered up or possib

Pagina 88 - Simulating the Transducer

Incorrect revision level of the device firmware.Read the three elements of the REVISION_ARRAY parameter, which are: • Stack board firmware • Stack board

Pagina 89 - Troubleshooting Guide

10.4 Device DiagnosticsLogix 3400MD Digital Positioner MemoryThe Logix 3400MD digital positioner contains a number of areas of memory. An EEPROM prov

Pagina 90

9 NEEDS_MAINT_SOON This indicates that the device needs maintenance soon. Diagnostics has indicated something is out of tolerance or is going to fail

Pagina 91

Table 10.7 Summary of Configuration ErrorsProblem/Fault Probable Cause Recommended ActionName of parameters are not visibleMissing or incorrect versi

Pagina 92 - Spool Valve

AO block is in the correct mode but does not seem to be operating1. Simulation active. 1. Disable simulation. See Sub-section 10.8 for procedure.2.

Pagina 93 - Advanced Features

Table 10.9 PID Function Block ParametersParameter Initial Value Valid Range Corrective ActionBYPASS 0 1:OFF,2:ON Initial value is a configuration error

Pagina 94 - 10.11 Stroke Characterization

Table 10.10 Setting the Simulation Dip SwitchTo Set the Dip Switch to:Enable read and write access to the device’s configuration. (Factory-set default

Pagina 95 - System Preparation

1. Set ENABLE_DISABLE to ACTIVE and write the parameter.2. Set SIMULATE_VALUE and SIMULATE_STATUS as desired and write the parameter.3. Read the READB

Pagina 96

• MANUFAC_ID: This should always equal Flowserve or 0x464c53 (4607059).• DEV_TYPE: This will be 0x0203 (515). This indicates the device is a Logix

Pagina 97 - 10.14 Signature Procedure

Sticking or hunting operation of the positioner. 1. Contamination of spool valve assembly 1. See Air Supply Requirements on page 15. See Spool Valve

Pagina 98 - Retrieve a Signature

Figure 10.2 Gain Effect DiagramThis algorithm allows for quicker response to smaller steps yet stable control for large steps. (Refer to Figure 10.2.)

Pagina 99

• Send a 50 percent command.• Set integral to zero.• Locate the DAC_PERCENT• Write this percentage value to IL_OFFSET.• Write original value to I

Pagina 100

8. Carefully slide the block over the spool, using the machined surface of the housing base as a register. Slide the block toward the driver module un

Pagina 101 - Glossary

40 93.4 9..57 4045 94.2 11.86 4550 94.8 14.15 5055 95.5 17.54 5560 96.0 20.93 6065 96.5 25.94 6570 97.0 30.95 7075 97.5 38.36 7580 98.0 45.77 8085 9

Pagina 102 - List of Figures

* Must not be selected if a custom curve is to be created or edited.10.12 Characterization ProcedureThe following procedure outlines the basic way se

Pagina 103 - List of Tables

Table 10.16 Transducer Block Signature ParametersParameter Description Value-Meaning CommentsMODE_BLKThe operating mode of the Transducer blockPermitt

Pagina 104

10.14 Signature ProcedureThe following steps are an example of how to initiate a ramp signature capture.1. Make sure the process is in a safe conditi

Pagina 105

STEP SIGNATUREIf a step signature was desired, simply do not select STEP_RAMP in SIG_FLAGS, and then set the STEP_TIME prior to selecting BEGIN_SIG.Co

Pagina 106 - FCD LGENIM3405-02 11/13

XDTB_MAIN_BLOCK 20 mSXDTB_MD_BLOCK 20 mSPID 90 mSDI_LO 20 msDI_HI 20 mSANALOG_OUT 30 mSDISCRETE_OUT 30 mSOUTPUT_SPLITTER 50 mSiNPUT _SEL

Comentarios a estos manuales

Sin comentarios