WCAIM2058 DataFlo Digital Electronic Remote Controller DRC17 17
Table 2
Parameter Minimum Maximum
Name Numeric Numeric List
Display Value Value Values Description Notes
Sec Code 0000 9999 Security code
Unit Adr 1 255 Communications address
Curr Rng 4-20 mA, 0-20 mA Optional current output module range
P-term 0 9999 Proportional term for controlling algorithm
I-term 0 999 Integral term for controlling algorithm
D-term 0 8000 Derivative term for controlling algorithm
Cyc Intr 1.0 s 999.9 s Cycle interval
Flt Time 0.8 s 60.0 s Filtering time window
Bkl Time 0 ms 9999 ms Gear backlash time
Trq Time 0 ms 9999 ms Torque time
Dead Bnd 0.1 20.0 Dead band
Action RISE, FALL Controller direct (RISE)/reverse (FALL) action
Cyc Res ON, OFF Cycle interval reset option
PrLo Alr -999 999 Process low alarm point
PrHi Alr -999 999 Process high alarm point
SigErPos 0.0 % 100.0 % HOLD, IGNORE Invalid signal position or action
FBErrAct IGNORE, FULL CW, Invalid shaft position reading action
FULL CCW
Pon Posn 0.0 % 100.0 % HOLD Power-on actuator shaft position
Pon Time 0 s 9999 s Power-on position dwell time
LoPosLim 0.0 % 100.0 % Lowest position valve is allowed to reach 2
HiPosLim 0.0 % 100.0 % Highest position valve is allowed to reach 2
Brk Time 0.10 s 0.99 s Time motor brake is applied when stopping
CyCount Valve cycle counter 1
HiPosAlr 0.0 % 100.0 % Valve shaft high position alarm point
LoPosAlr 0.0 % 100.0 % Valve shaft low position alarm point
Com Rate 1200, 2400, 4800, Serial communications bit rate
9600, 19200, 38400
PrLo Eng -999 999 Process lower value in engineering units 4
PrHi Eng -999 999 Process upper value in engineering units. 4
SpLo Eng -999 999 Setpoint lower value in engineering units 3
SpHi Eng -999 999 Setpoint upper value in engineering units 3
Dflt Val YES, NO Option to default all programmable parameters
NOTES
1. The cycle counter cannot be programmed. It can be cleared in the Program Mode by editing the value and pressing both the and keys
simultaneously. 2. This parameter restricts valve movement to between the two values. The lower shaft limit must be less than the upper shaft
limit. 3. The setpoint limit must lie within the range of the Process Engineering Units. 4. When the process lower and upper value are edited,
pressing both the and keys simultaneously will change the system decimal point. The possibilities for decimal point location are xxx, xx.x,
x.xx, and 0.xxx.