Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11
flowserve.com
Preparation
1. Connect internal heaters, if supplied.
2. Replace all plastic caps or plugs with metal pipe plugs.
3. Ensure all covers are tight.
LY Storage Orientation
1. Store with the Control Compartment Cover (Limit Switch compartment) facing upward. Do not
store units on their side.
2. Store off the floor on suitable skids and cover with an unsealed dust cover leaving the bottom open
and air holes in the side.
Storage Inspection and Correction
1. Perform a semi-annual visual inspection. A minimum inspection should include checking the
following:
•Packaging •Plugs
•Covers •Dryness
•Cleanliness •Heatsource(ifused)forproperfunctioning
2. Record and correct deficiencies noted during inspection.