Flowserve NRGS15-1 Manual de usuario

Busca en linea o descarga Manual de usuario para Hardware Flowserve NRGS15-1. Flowserve NRGS15-1 User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir

Indice de contenidos

Pagina 1 - NRGS 15-1 

GESTRA Steam SystemsNRGS 15-1 Installation Instructions 818479-00Level Switch NRGS 15-1

Pagina 2 - Contents

10Explanatory Notes – continued –Technical dataService pressure25 barg at 224 °CConnectionScrewed 1" BSP, DIN ISO 228MaterialsScrew-in housing: 1

Pagina 3

11Explanatory Notes – continued –Technical data - continued -Indicators and adjustors3 red LEDs to indicate "Low level alarm 1 + 2 / High level&q

Pagina 4 - Dimensions

12Explanatory Notes – continued –Technical data - continued -Name Plate 110-120 and 220-240 VACCorrosion resistanceIf the NRGS 15-1 is used for its i

Pagina 5 - Functional Elements

13Establishing FunctionsSelect functionBefore installing and commissioning the NRGS 15-1 ascertain the settings for the required functions.Five functi

Pagina 6

14Establishing Functions – continued –Select function - continued -Factory settingThe factory setting of level switch NRGS 15-1 without pushbuttons i

Pagina 7

15Establishing Functions – continued –Adjust function1. Undo the housing screws and remove the housing lid.2. Set the code switch to the desired fu

Pagina 8 - Important notes

16InstallationLevel switch NRGS 15-1We highly recommend that only qualified staff should carry out installation work in accord-ance with these install

Pagina 9 - Explanatory Notes

17Installation – continued –Align terminal boxAlign the terminal box such that the LEDs , , , , can be seen by the operator.1. Undo the housing scre

Pagina 10 - – continued –

18Installation – continued –Mount terminal box1. Put gasket onto electrode part.2. Run all electrode wires through the hole for the fixing screw (see

Pagina 11 - - continued

19WiringConnect level switch NRGS 15-1Use multi-core flexible control cable with a min. conductor size of 0.75 mm² as mains and control cables. 1. Und

Pagina 12 - Corrosion resistance

2ContentsPageImportant notesUsage for the intended purpose...8Safe

Pagina 13 - Establishing Functions

20Wiring – continued –Wiring diagram456789101113234143214321141512Mains supplyTESTRESETPE connectionElectrodecablesFig. 6

Pagina 14 - 123 54678910

21CommissioningCheck wiring1. Make sure that the level switch is correctly wired in accordance with the wiring diagram (see Fig. 6).2. Make sure that

Pagina 15 - 123 54 678910

22Commissioning – continued –Check switching functionsUse the following table as reference when checking the individual switching functions. Electrode

Pagina 16 - Installation

23Commissioning – continued –Check switching functions - continued -Electrode rod3 = timed pump control (fill control)Electrode rod3 emerges Relay3 is

Pagina 17 - Installation – continued –

24Malfunctions / TroubleshootingFault finding listSwitchpoint "Pump OFF" exceeded - no functionFaul t: Mains voltage is not applied.Remedy:S

Pagina 18

25Malfunctions / Troubleshooting – continued –Replace electronic circuit board1. Undo the housing screws and remove the housing lid . 2. Pull the ele

Pagina 19

26AnnexAdjust other functionsThe level switch assigns one switching channel to each electrode tip. The functions of the switching channels 1 and 4 are

Pagina 20 - Wiring – continued –

27Annex – continued –Installation in non-metallic vesselThe level switch electrode can also be installed in non-metallic vessels. Note that in this ca

Pagina 21 - Commissioning

28Examples of InstallationKeyFlange PN40, DN50, DIN 2527 or flange PN40, DN100, DIN 2527For the approval of the boiler standpipe with connecting flang

Pagina 23

3ContentsPageAnnexAdjust other functions ...26Install

Pagina 24

808597-00/804 agt ©2004 GESTRA AG Bremen Printed in Germanywww.gestra.deGESTRA AGPostfach 10 54 60, D-28054 Bremen Münchener Str. 77, D-28215 Bremen

Pagina 25

4Dimensions180~355 100013012Fig. 1b = 60A. F. 411" BSP to DIN ISO 228

Pagina 26

5Functional Elements50>1465-701234ABCN8N100.51" BSP to DIN Ø 40Fig. 2Fig. 3D40A. F. 41E

Pagina 27 - Annex – continued –

6Functional Elements4567891011131415121245674567JFig. 4Fig. 5FGIJKLMNH4321123 456789OMAX 70 °CMAX 95 %%IP 65

Pagina 28 - Examples of Installation

7KeyLED 1 redLED 2 redLED 3 yellowLED 4 redLED "Mains supply ON" greenCode switch S1Potentiometer for time delay (0 to 30 sec.)TEST buttonRE

Pagina 29 - For your notes

8Important notesUsage for the intended purposeThe level switch NRGS 15 - 1 is designed for detecting and signalling levels in liquids with a minimum e

Pagina 30 - GESTRA AG

9Explanatory NotesScope of supplyNRGS 15-1 1 Level electrode with four tips 1 Terminal box with integrated level switch 1 Joint ring Ø33x39 to DIN

Comentarios a estos manuales

Sin comentarios