Principles of Operation:
The Apex W7000 positioner causes rotation (or linear movement) of valve actuator in proportion to an input signal.
This signal may take the form of pneumatic pressure (Model W7000 and W7600) or electric current (Models
W7100,W7200 W7400 W7500). Supply pressure is directed to the actuator through a precision spool valve. As input
pressure is varied, the balance beam shifts away from its neutral position. The spool also shifts and a differential
pressure is created across the actuator causing rotation (or linear movement). Actuator motion is fed back through the
positioner shaft and cam. Cam rotation causes movement of the feedback arm, changing compression in the
feedback spring, forcing the balance beam and spool back to their neutral position. This shuts off the flow of air to the
actuator and rotation stops.
Installation:
The Apex W7000 positioner can be installed on rotary and linear actuators. Actuators can be either double acting or
spring return. Positioners can be set up for rotation in either direction (direct or reverse acting).
Supply Air Requirements:
Air pressure must be limited to 150 psi for supply and 30 psi for instrument signal to avoid damage to the positioner.
Supply air must be clean, dry and oil free instrument quality air in accordance with ISA S7.3 specifications (dew point
>18 degrees below ambient temperature, particle size <5 microns, oil content <1ppm.
Mounting:
The following instructions apply to rotary actuators only. Linear applications require special mounting and coupling
(consult factory).
1. Mount bracket to actuator. Tighten bolts finger tight only at this time. A standard bracket is available for
mounting to NAMUR compliant actuators.
2. Install coupler (not required if installing to a NAMUR compliant actuator) on actuator shaft making sure it is
centered.
3. Verify that orientation of actuator (and coupler) flats match positioner shaft flats. If necessary, rotate the cam
before installing positioner (see “Cam Installation”). NOTE: Actuator should be in orientation corresponding to
zero input signal.
4. Install positioner onto bracket. Make sure positioner shaft and coupler are engaged and centered. Tighten bolts
finger tight only at this time.
Pneumatic Connections: All pneumatic connections, the supply, both output ports, and instrument ports are
female ¼” NPT. All connections require user-supplied tubing fittings. Caution: Do not use Teflon tape as a pipe
thread sealant. Use only a liquid or paste non-hardening pipe sealant on the threads.
5. Connect positioner ports C1 and C2 to actuator. Port C2 is always connected to the actuator port used to drive
actuator away from its start or fail position (the factor cam setting is full clockwise at minimum input). Port C1 is
connected to the opposite port or may be plugged for spring return actuators. Note: For fail counterclockwise
applications, the cam must be flipped over so the “R” side is facing upwards (see “Cam Installation”).
WORCESTER CONTROLS
Installation
Operation
Maintenance
APEX W7000 Pneumatic Positioner
FCD WCENIM2077-01
Vista de pagina 0
1 2 3 4 5 6 ... 11 12

Indice de contenidos

Pagina 1 - Maintenance

1 S Principles of Operation: The Apex W7000 positioner causes rotation (or linear movement) of valve actuator in proportion to an input signal.

Pagina 2

10 APEX W7000 SYSTEM -I/P CONVERTERS -DOME INDICATOR -GAUGES -SWITCHBOXES

Pagina 4 - Cam Adjustment/Replacement:

12 Representative: Bulletin FCD WCENIM2077-01 Flowserve Corporation 1978 Foreman Drive Cookeville, Tennessee, USA, 38501 931 432-4021 Flowse

Pagina 5

2 6. Connect supply air to port marked “S”. 7. Connect instrument signal air to the port marked “I” for model W7000 and W7600. For models

Pagina 6 - Electrical Specifications

3 Calibration Procedure: 1. Apply 0% input signal (0% = 20 kPa, 3 psi, or 4 mA). 2. Wait for steady state. It is important to wait for stead

Pagina 7 - Maintenance:

4 Cam Installation: Introduction: The standard cam (labeled “K1” features linear, 90 degree operation for full 3-15 psi input, 3-9 and 9-15 psi

Pagina 8

5 Split Range lobe is used to achieve high resolution in split range applications, where only a portion of the signal is used to obtain 90 degree

Pagina 9

6 Electrical Specifications Model Agency Approvals Hazardous Location Rating1 Max Voltage (vdc) Min. Voltage (vdc) Max. Current (mA) W7000 N

Pagina 10 - APEX W7000 SYSTEM

7 Filter Plug Replacement: Caution: Do not operate the unit without filter and filter plug installed. Do not attempt to unscrew filter plug whi

Pagina 11

8 SPARE PARTS APEX W7000 DWG FLS Description Qty No p/n 1 Housing N/A 2 X01370 Front cover incl. O-ring and screws 1 3 X01371 Connec

Pagina 12 - Representative:

9 6 X01375 Gasket W7100 1 7 X01376 Diaphragm cover incl. O-ring 1 8 X01377 Diaphragm 1 9 X01378 Diaphragm washer 2 10 X01379 Balance arm 1 13 X01380