28 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00
Flow Control Division
Limitorque Actuation Systems
Figure 6-3: The second Configure MOV Network screen
Touching an “Edit” button will take the user to a screen similar to Figure 6-4. Each screen provides information about the
parameter being configured, the current value, and the valid values or range.
Figure 6-4: The Timeout Edit screen
The remaining eight screens under the Configure MOV Network section allow the user to select, graphically, which MOVs
are active (Figure 6-5).
Timeout
Current Value:
350
200-5000 (ms)
Valid Range:
MOV response
time-out period.
1 ms increments
(Min. 200 msec.)
350
<< Back
7
89
6
5
4
1
2
3
0.
CLR
DEL
-
E
N
T
EDIT
EDIT
EDIT
EDIT
EDIT
EDIT
Timeout (ms): 350
Prop. Delay (ms): 10
RTS ON Delay (ms): 10
Total Active MOVs: 32
First Conf. MOV: 1
Last Conf. MOV: 32
Configure MOV Network
<< Back
Next >>