Flowserve Logix 3200IQ Digital Positioner Manual de usuario Pagina 2

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 32
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 1
Flowserve Corporation 1350 N. Mountain Springs Parkway 1978 Foreman Dr.
Flow Control Division Springville, Utah 84663-3004 Cookville, TN 38501
www.flowserve.com Phone: 801 489 2233 Phone: 931 432 4021
FCD AXAIM3200-00 9/04 Page: 2 of 32
© 2004, Flowserve Corporation, Printed in USA
Automax Logix 3200IQ Digital Positioner
Installation, Operation and Maintenance Instructions
Figure 1: Logix 3200IQ Digital Positioner
Positioner Overview
The Logix 3200IQ digital positioner is a two-wire
4-20 mA input digital valve positioner. The positioner is
configurable through the local user interface. The Logix
3200IQ utilizes the HART protocol to allow two-way
remote communications with the positioner. The Logix
3200IQ positioner can control both double- and single-
acting actuators with linear or rotary mountings. The
positioner is completely powered by the 4-20 mA input
signal. Start up current must be at least 3.6 mA without
AO card or 3.85 mA with AO card.
Specifications
Table I: Electrical Specifications
Power Supply Two-wire, 4-20 mA
10.0 to 30.0 VDC
Compliance Voltage 10.0 VDC @ 20 mA
495 @ 20 mA Typical
Effective Resistance Add 20 when HART
communication active
Communications HART Protocol
Minimum Operating 3.6 mA without AO board
Current 3.85 mA with AO board
Maximum Voltage 30.0 VDC
Table II: SoftTools Suite Software Specifications
Computer Minimum Pentium processor running
Windows 95, 98, NT, 2000, XP, 32 MB
total memory (64 MB recommended),
30 MB available hard disk space,
CD-ROM drive
Ports 1 minimum available with 8 maximum
possible. (Can also communicate via
PCMCIA and USB connections)
HART Modem RS-232/PCMCIA card/USB
HART Filter May be required in conjunction with
some DCS hardware
HART MUX MTL 4840/ELCON 2700
Table III: Environmental Conditions
Standard
-4° to 176°F
Operating Temperature (-20° to 80°C)
Range
Low
-40° to 176°F
(-40° to 80°C)
Transport and Storage
Temperature Range
-40° to 176°F (-40° to 80°C)
Operating Humidity 0 to 100% non-condensing
Note: The air supply must conform to ISA Standard
ISA 7.0.01 (a dew point at least 18 degrees Fahrenheit
below ambient temperature, particle size below five
microns – one micron recommended – and oil content
not to exceed one part per million).
Table IV: Physical Specifications
Housing Material Cast, powder-painted aluminum,
stainless steel
Soft Goods Buna-N / Fluorosilicone
Weight
8.3 pounds (3.9 kg) aluminum
20.5 pounds (9.3 kg) stainless steel
Table V: Positioner Specifications
Deadband <0.1% full scale
Repeatability <0.05% full scale
Linearity
<0.5% (rotary), <0.8%,
(sliding stem) full scale
Air Consumption
<0.3 SCFM (0.5 Nm
3
/hr)
@ 60 psi (4 barg)
Vista de pagina 1