Button functions:
Press 5 sec = Calibration
Press x3 = Direct/reverse action
Press x4 = Show gain setting
Press x5 - x11 = Change gain
setting
To indicate that a command is
accepted, the three LED:s
light up.
9.6 Change of gain setting
To lower the gain, press the button: 7, 6
or 5 times (5= lowest).
To increase the gain (if actuator is
moving to slow).
Press the button: 9, 10 or 11 times (11=
highest) to increase the gain.
The LED:s flashes alternately when the
button is pressed. After gain change the
LED:s show the gain code (see 9.3) five
times.
The default value after first calibration is
D .
After this, the gain settings are finished.
x11 G (Highest)
x10 F
x9 E
x8 D Default
x7 C
x6 B
x5 A (Lowest)
Lower Higher