8
®
User Instructions Logix 510si - LGENIM0510-02 12/13
NOTE: The switch settings in the Configuration box
are activated only by pressing the Quick-Cal button.
Operation of CONFIGURATION DIPswitch Setup -The
first 5 DIP Switches are for basic configuration.
a. Air Action - This must be set to match the configuration
of the valve/actuator mechanical tubing connection and
spring location since these determine the air action of
the system.
ÊUÊATO (air-to-open)- Selecting ATO if increasing
output pressure from the positioner is tubed so
it will cause the valve to open.
ÊUÊATC (air-to-close)- Selecting ATC if increasing
output pressure from the positioner is tubed so
it will cause the valve to close.
b. Signal at Closed - Normally this will be set to 4 mA for
an Air-to-open actuator, and 20 mA for an Air-to-close
actuator configuration.
Ê -iiVÌ}Ê{ÊÊÜÊ>iÊÌiÊÛ>ÛiÊvÕÞÊVÃi`ÊÊ
when the signal is 4mA and fully open when the
signal is 20 mA.
Ê -iiVÌ}ÊÓäÊÊÜÊ>iÊÌiÊÛ>ÛiÊvÕÞÊVÃi`ÊÊ
when the signal is 20 mA and fully open when
the signal is 4 mA.
c. Characteristic
Ê -iiVÌÊi>ÀÊvÊÌiÊ>VÌÕ>ÌÀÊ«ÃÌÊÃÕ`ÊLiÊÊ
directly proportional to the input signal.
Ê /iÊr¯Ê«ÌÊÜÊV>À>VÌiÀâiÊÌiÊ>VÌÕ>ÌÀÊÊ
response to the input signal based on a stan-
dard 30:1 equal percent rangeability curve.
d. Tight Shutoff
Ê -iiVÌÊ"ÊÌÊ>ÛiÊÌiÊ«ÃÌiÀÊvÕÞÊÃ>ÌÕÀ>ÌiÊÊ
the actuator closed at a signal less than 1%.
Ê -iÌÌ}ÊÌiÊÃÜÌVÊÊÌiÊ"vvÊ«ÃÌÊ`Ã>LiÃÊÊ
this feature.
e. Auto Tune -This switch controls whether the positioner
will auto tune itself every time the quick cal button is
pressed
On enables an automatic tuning feature that will auto-
matically determine the positioner gain settings every
time a “Quick-Cal” is performed. The gain settings can
be modified after a calibration by adjusting the rotary
“Gain” switch.
NOTE: there is a small black arrow indicating the selec-
tion. The slot does not indicate the chosen gain.
Figure 4: Logix 510si Local Interface
Configuration
Switches
Gain selector
4-20 mA Input
4-20 mA Feedback
(Optional)
Jog Calibrate
Buttons
LED Status
Lights
Quick-Cal
Switch
Calibration
Switches
Indicator arrow