The Status Menu is used to select whether or not the positioner is in service.
The menu contents are shown in the figures on the right and the various
texts are described below:
o o service Not in service.
Flashing indicator in upper left-hand corner of display.
in service Positioner in service.
Critical parameters cannot be changed.
The Setup Menu is used for various settings.
The menu contents are shown in the chart on the next page and the various texts are described below:
Only for linear actuator.
Lever stroke Stroke length to achieve correct display.
Level cal Calibration of positions to achieve correct display.
Direction
Direct Direct function (signal increase opens). Indicator/spindle rotates counter- clockwise.
Reverse Reverse function.
Character Curves that show position as a function of input signal.
Linear
Equal %
Quick Open
Square Root
Custom Create Own Curve
Custom Characterization # of points (Specify # of pts, 3,5,9,17 or 33)
Custom Curve: Enter values on X and Y axis.
Current Range: 0%=4mA, 100%= 20mA
Possibility of selecting which input signals correspond to 0% and 100%
movement respectively. Examples of settings: 4mA = 0%, 12mA =
100%, 12mA = 0%, 20mA = 100%