Digital Electronic Controller DFC17 Installation, Operation and Maintenance Instructions 19
Program Mode Menu
Display Description Mininum Value Maximum Value
CodE Security code for access to Program, Calibration 0000 9999
and Manual Setpoint modes.
Addr Communications unit address 1 255
PtEr Proportional Control Term 0000 9999
itEr Integral Control Term 000 999
dtEr Derivative Control Term 0000 8000
onH Motor Cycle Interval 1.0 sec 999.9 sec
FiLT Process Signal Filter Time 0.8 sec 60.0 sec
bLt Gearbox Backlash Time 0 ms 9999 ms
tort Gear Torque Time 0 ms 9999 ms
dEbA Controller Dead Band 0.1 20.0
ACt Controller Action – RISE or FALL
CyCr Cycle Interval Reset – ON or OFF
FPOS Process or Setpoint invalid reading action – 0.0% 100.0%
HOLD, NONE, or a position value.
SAct Invalid feedback pot reading action – GOC (go clockwise),
GOCC (go counter-clockwise), HOLD, or NONE.
yA Lower shaft position limit 0.0% 100.0%
yE Upper shaft position limit 0.0% 100.0%
br Brake ON time. 0.10 sec 0.99 sec
CyCn Run Time Cycle Count (reading represents thousands of cycles).
AHi Over-travel Alarm 0.0% 100.0%
ALo Under-travel Alarm 0.0% 100.0%
PrLo Process Low Alarm Value PENL PENU
PrHi Process High Alarm Value PENL PENU
bAUD Communications Baud Rate 1200 bps 38.4 Kbps
PrS9 Process Signal Selection – PR1, PR2, or BOTH
PEnL Process Engineering Units Range (Lower) -999 999
PEnU Process Engineering Units Range (Upper) -999 999
SEnL Setpoint Engineering Units Range (Lower) -999 999
SEnU Setpoint Engineering Units Range (Upper) -999 999
PrSt Restore Default Parameters (YES or NO)
Note: A decimal point may be entered when entering PEnL and PEnU values, if the controlled range falls between -99.9 and 99.9. This has the
effect of improving resolution for small process ranges (i.e., 0.0 to 10.0 GPM). See Controller Specification on floppy disk for more detail.