Flowserve DFC17 Manual de usuario Pagina 23

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 28
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 22
WCAIM2026
DataFlo
Digital Electronic Controller DFC17 Installation, Operation and Maintenance Instructions 23
5.0 TECHNICAL DATA
5.1 Allowable Supply Voltage Range
All voltages +/- 10%
Power Consumption (Circuit board only) – 2.5 Watts
5.2 Analog Input Circuit Specifications
Maximum Tolerated Noise Level at Maximum Controller
Resolution/ Sensitivity – Approx. 3.5 mV (16 microamps).
Resistance Input
DFC-1K – Nom. 1000 ohms
DFC-13 – Nom. 135 ohms
Current Input
DFC-1 – 1 to 5 milliamps
DFC-4 – 4 to 20 milliamps
DFC-10 – 10 to 50 milliamps
Voltage Input
DFC-5V – 0 to 5 VDC
DFC-XV – 0 to 10 VDC
5.3 Output Circuit Specifications
All Models
Maximum Surge Current 100 amps for 1 cycle
Maximum Normal Starting or
In-rush Current 10 amps for 1 second
Maximum Stall Current 8 amps for 1 minute
Maximum Running Current – Resistive Load 5 amps
90% Duty Cycle
Maximum Running Current – Inductive Load 3 amps
90% Duty Cycle
Maximum Peak Voltage at Load Circuit 800 VAC
(All 120 & 240 VAC Models)
Maximum Driver Circuit Current 3 amps Continuous
(All 12 & 24 VDC Models)
Alarm Output 100 mA maximum current
at 50 volts DC maximum
5.4 Input Circuit Load Resistances
1 to 5 milliamp Models Approx. 1000 ohms
4 to 20 milliamp Models Approx. 220 ohms
10 to 50 milliamp Models Approx. 100 ohms
0 to 5 VDC Models Approx. 800 ohms
0 to 10 VDC Models Approx. 1100 ohms
Flow Control Division