Push cleaning device 4 Fig. 5 slowly into the mid position in order to simulate a malfunction.
The amber system LED is flashing and the relay contact Alarm 2 opens. Error code e1 or e2 is
indicated.
Push cleaning device 4 Fig. 5 back into its initial position.
The equipment must switch back to normal operation.
Functional test
Start, Operation, Alarm and Function Test – continued –
If the alarm limits 1 and 2 are exceeded, the adjusted time delay is activated.
LED Alarm 1 and LED Alarm 2 are flashing. After the time delay LED Alarm 1 and LED Alarm 2 are
permanently illuminated. The relay contacts Alarm 1 and Alarm 2 open.
Alarm 2 is also indicated when
■ the separator is switched off,
■ the purging valve Clw is opened and
■ if the sensor ORG 12 signals a malfunction
Depending on the reason that caused Alarm 2, the equipment
state “ppm>Limit”, “Separator OFF” or “Clear Water On” will
be indicated in the measurement window.
Alarm 1 and 2
OIL CONTENT :
ppm
State: ppm > Limit
16
UTC 10:46 2006-12-06