Wiring
TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68
Use screened four-core cable for wiring, e. g. Ölflex 110 CH, produced by Lapp, 4x0.5 mm². Max. cable
length between temperature sensor and temperature transmitter TRV 5-40: 25 m.
Connecting the measuring element
1. Take cover off the terminal box .
2. Unscrew dome nut of the cable gland and take out the lamellar insert Fig.10.
3. Cut off outer cable sheath and expose braided screen over a length of approx. 10-15 mm.
4. Push dome nut and lamellar insert with sealing ring onto the cable .
5. Bend braided screen outwards at a right angle (90°).
6. Fold braided screen towards outer sheath, i. e. by another 18.
7. Push lamellar insert with sealing ring into gland body and turn it briefly around both sides of
the cable axis and snap anti-rotation element into place.
8. Firmly screw on dome nut .
9. Connect the connecting cable in accordance with the wiring diagram to the measuring element .
10.Replace cover and tighten screw securely.
Key
Dome nut
Sealing ring
Lamellar insert
Braided screen
Gland body
Screened cable