11
Attention
To protect the switching contacts fuse circuit with T 2.5 A or according
to TRD regulations (1.0 A for 72 h operation).
The screen must not make any other electrical contact.
Note
Connect screen only to terminal [10] of the temperature switch.
The loop resistance must be lower than 10 .
The rated voltage is stated on the name plate.
When switching off inductive loads, voltage spikes are produced that
may impair the operation of control and measuring systems. Inductive
loads should therefore be provided with commercial arc suppressor
RC combinations, e. g. 0.1 µF/100 .
Wiring
Wiring Diagram
See wiring diagram page 2.
Tool
Screwdriver for slotted screws, size 2.5, completely insulated according to
VDE 0680.
TRS 5-8 b
Use screened four-core supply cable for wiring, e. g. 2 x 2 x 0.8 mm or 4 x 0.5 mm
2
.
1. Connect terminal strip according to wiring diagram. Fig. 1
2. Connect additional display units to terminals marked in yellow and black of the
TRG 5-54, TRG 5-56 and TRG 5-58. Fig. 7