Basic Settings – continued –
0 % /100 % calibration for capacitance level monitoring system
Press button three times briefly to enter
the window for calibrating the 0 % and
100 % settings.
Press button twice briefly to enter the
line editing mode.
Lower the water level in the vessel
to 0 %.
The split-screen main window shows
which GESTRA bus devices can be
displayed:
High level limiter NRS 1-41
Low level limiter NRS 1-40
Level switch NRS 2-40
Level controller NRR 2-40
Conductivity controller LRR 1-40
Before commissioning the installation
establish the measuring range of the
capacitance level electrode NRG 26-40 by
calibrating the 0 % and 100 % settings.
flashing
3 times briefly
twice briefly