Basic Settings – continued –
Calibrating the feedback potentiometer of an external control valve – continued –
Press and hold down button until the
control valve is closed.
Press button once briefly to save the
current resistance value of the feedback
potentiometer as 0 % setting (valve
closed).
Press button three times briefly to
activate the line editing mode for
calibrating the signal of the feedback
potentiometer.
flashing
flashing
3 times briefly
hold down
once briefly