Electrical Connection
Wiring via four-pole connector.
Screened four-core cable, e. g. I-Y(St)Y 2 x 2 x 0.8 or LIYCY 4 x 0.5 mm².
Max. length 100 m with conductivities from 10 μS/cm.
Max. length 30 m with conductivities from 0.5 μS/cm.
Max. length 15 m with conductivities from 0.5 μS/cm and application of the ancillary unit URN 1
(24 V DC).
1. Loosen screw
5, Fig. 6.
2. Take the terminal box off the level electrode, leaving the sealing element
9 on the contact plate 0.
3. Remove cover
6.
4. Press connecting plate
8 out of the upper part of the terminal box 7.
The upper part of the terminal box can be turned in steps of 90°.
5. Detach cable gland and cable clamp
! from the upper part of the terminal box 7.
6. Run cable through cable gland
" and upper terminal box 7 and connect the terminals of the
connecting plate 8 according to the wiring diagram.
7. Press connecting plate
8 into the upper part of the terminal box and align the cable.
8. Hold cable with cable clamp
! and cable gland " in position.
9. Mount cover
6 and insert screw 5.
10. Put upper part of the terminal box onto the level electrode and fix it firmly with screw
5.
ER 50-1, ER 56-1
Tools
Screwdriver for cross-recess head screws, size 1
Screwdriver for slotted screws, size 2.5, completely insulated according to DIN VDE 0680
Open-end spanner 17 mm A. F.
Wiring diagram
Fig. 11