15
Note
In mode 3 two measuring electrodes NRG 16-19 (one for banking-up of condensate and
one for steam loss) per measuring channel are connected together so that e. g. a float trap
can be monitored. For more information see the installation instructions for NRG 16-19,
NRG 16-27, NRG 16-28.
In mode 6 and 7 the measuring electrodes NRG 16-27, NRG 16-28 receive the measure
-
ments of the condensate temperature only from the integrated temperature sensor.
Commissioning – continued –
Establishing the number of measuring channels
Use code switch 6 Fig. 4, switches S4 – S7 to set the number of measuring channels.
The switches S8 – S0 must remain in the OFF position.
6
1 098765
4
32
NO
Schaltwippe weiß
S4 S5 S6 S7 Channels S4 S5 S6 S7 Channels
OFF OFF OFF OFF 1 OFF OFF OFF ON 9
ON OFF OFF OFF 2 ON OFF OFF ON 10
OFF ON OFF OFF 3 OFF ON OFF ON 11
ON ON OFF OFF 4 ON ON OFF ON 12
OFF OFF ON OFF 5 OFF OFF ON ON 13
ON OFF ON OFF 6 ON OFF ON ON 14
OFF ON ON OFF 7 OFF ON ON ON 15
ON ON ON OFF 8 ON ON ON ON 16
Note
If the settings of S1 – S7 are changed during operation, the new settings will only be
accepted by the test station after the supply voltage has been switched off and on.
Switching on supply voltage
Switch on supply voltage. The seven-segment display and the LEDs will be tested, i. e. all segments
and LEDs will be illuminated/flashing.
Code switch, white