Operation, Alarm and Test – continued –
y y y
Serial
poll
Key E
briefly →
← longer
HIS
Keys
(1)
↓ (3) ↑
InT
Keys
(1)
↓ (3) ↑
CAL
Key E
briefly →
← longer
ALL
Key E
briefly →
Temperature
auto poll
auto →
don
←
CAL
Keys
(1)
↓ (3) ↑
Keys
(1)
↓ (3) ↑
C.xx
Key E
briefly →
← longer
Change
temperature
Keys (1), (3)
Key E
briefly →
don
←
C.xx
dtC
Key E
briefly →
← longer
Change
tempera-
ture
Keys (1), (3)
Key E
briefly →
don
←
dtC
Setting banking-up of condensate, mode 2 and 7
The precondition for this operating mode is:
n the use of the measuring electrodes NRG 16-27, NRG 16-28 (with integrated condensate
temperature measurement at the steam trap)
With the parameter dtC the factory set difference of 40 K between the temperature measured at the
steam trap and the switchpoint “Banking-up of condensate”. The value can be changed in increments
of 1 K up to a max. limit of 100 K.
In the parameter mode CAL the condensate temperature from all steam traps is polled, the difference
dtC is subtracted and the result saved.
Starting from the parameter mode ALL, the switchpoint “banking-up of condensate” can be adjusted in
increments of 5 K for each individual steam trap (C.xx) in order to match the settings optimally to the
operating conditions.