18
Causes
Faulty installation and/or configuration of CAN bus components, excessively high temperatures in
devices, defective electronic component parts or electromagnetic interferences of the supply system
can result in system malfunctions.
Other malfunctions are:
n Incorrect communication in the CAN bus system
n Overloading of the 24 V power supply unit that is integrated in the control unit
System Malfunctions
Note
Before carrying out the system malfunction analysis please check:
Wiring:
Is the wiring in accordance with the wiring diagrams?
Is the polarity of the bus lines always correct?
Are the bus lines of the first and the last devices provided with 120 Ω terminating
resistors?
Configuration of the level electrode NRG 1x-40 (Low water level LW):
Are the wire bridges (equipment 1 or 2) set correctly?
Does the position of the wire bridge correspond with the node ID setting?
Configuration of the temperature transmitter TRV 5-40:
Is the temperature transmitter TRV 5-40 set correctly as equipment 1, 2, 3 or 4?
Node ID:
Are all node ID settings correct?
Note that no node ID setting must be used twice!
Baud rate:
Does the baud rate setting correspond with the cable length?
Is the baud rate setting of all devices identical?