25
Annex – continued –
Table “Node ID”
In a CAN bus system a maximum of 123 nodes (devices) can be administered. Each node has its own
address (node ID). This address can be set via a 10-pole code switch
F Fig. 3.
Node ID 5
S1
ON 1
S2
OFF 2
S3 ON 4
S4 OFF 8
S5 OFF 16
S6 OFF 32
S7 OFF 64
(Factory setting)
Node ID 10
S1
OFF 1
S2
ON 2
S3 OFF 4
S4 ON 8
S5 OFF 16
S6 OFF 32
S7 OFF 64
(Example)
S 8 S 9 S 10 Baud rate Cable length
OFF ON OFF 250 kBit/s 125 m
Factory setting
ON ON OFF 125 kBit/s 250 m
OFF OFF ON 100 kBit/s 335 m
ON OFF ON 50 kBit/s 500 m
OFF ON ON 20 kBit/s 1000 m
ON ON ON 10 kBit/s 1000 m
Table Baud rate
F
Toggle switch, white
F
Toggle switch, white
Comentarios a estos manuales