Annex – continued
Table Node ID
In a CAN bus system a maximum of 123 nodes (devices) can be administered. Each
node has its own address (node ID). This address can be set via a 10-pole code switch .
(Factory setting) (Example)
(Factory setting 250 kBit/s)
Change factory setting
Use operating device URB or SPECTORcontrol to configure, parameterize, operate and
show the control parameters.
Node ID 50 Node ID 76
S1 OFF 1 S1 OFF 1
S2 ON 2S2OFF2
S3 OFF 4 S3 ON 4
S4 OFF 8 S4 ON 8
S5 ON 16 S5 OFF 16
S6 ON 32 S6 OFF 32
S7 OFF 64 S7 ON 64
S8 S9 S0 Baud rate Cable length
OFF OFF OFF 1000 kBit/s 25 m
ON OFF OFF 500 kBit/s 100 m
OFF ON OFF 250 kBit/s 250 m
ON ON OFF 125 kBit/s 500 m
OFF OFF ON 100 kBit/s 670 m
ON OFF ON 50 kBit/s 1000 m
OFF ON ON 20 kBit/s 1000 m
ON ON ON 10 kBit/s 1000 m
D
ON
123 54678910
D
ON
123 54 678910