26
TRVL range Setting end positions
0%=0.0% Select Out of Service.
Set percentage value
for desired end posi-
tion (e.g. 3%).
Set 0% Select In Service.
Connect calibrator.
Move forward to desired
end position (0%) and
press OK.
100%=100.0% Select Out of Service.
Set percentage value for
desired end position (e.g.
97%).
Set 100% Select In Service.
Connect calibrator. Move
forward to desired end
position (100%) and
press OK.
Trvl ctrl Behaviour at set end
position
Set low Choose between Free (go
to mechanical stop),
Limit (stop at set end
position), and Cut off (go
directly to mechanical
stop at set end position).
Set high Similar to Set low.
Values Select position for Cut off
and Limit at the
respective end positions.
Passcodes Setting passcodes for
various functions
Full menu Passcode for access to
full menu.
Write prot Passcode for removing
write protect.
Expert Passcode for access to
Expert menu
(TUNING).
Fact set Passcode to return to
default values applicable
when positioner was
delivered.
Numbers between 0000 and 9999 can be used as
passcodes. 0 = no passcode required.
Appearance On display
Language Select menu language.
Units Select units.
Def. Display Select value(s) to be
displayed during service.
The display reverts to
this value 10 minutes
after any change is made.
Start menu Start in Basic menu or
Full menu.
Contrast Adjust display contrast.
Orient Orientation of text on
display.
Par mode Display of control para
meters such as P, I, D or
K, Ti, Td.
Devicedata
HW rew
SW rew General parameters.
Capability
HART Menu with HART para-
meters. Only amendable
with HART communi-
cator. It is possible to read
from display.
Profibus
Status Indicates present status
Device ID Serial number
Address 1-126
Ta g Allotted ID
Descriptor ID description
Date N/A
Failsafe Value = preset pos
Time = Set time +10sec=
time before movement
Valve act = failsafe
(preset pos) or lastvalue
(present pos)
Alarm out= On/Off