Menus of Inputs/Outputs – continued –
NRG 26-40 calibration
1. In the menu NRG 26-40 CAN 1...10 press .
2. Choose a reference point at the boiler
(e. g. bottom edge of sightglass), fill the
boiler up to this point and then press but-
ton 0% Calibration to acknowledge.
3. After calibrating the zero point, 100% must
be calibrated. For this purpose click in the
green input field.
4. Use the on-screen keyboard to overwrite
or modify the value in the input mask.
5. Choose a value between >50% (e. g. mid-
dle of sightglass) and <100% (e. g. top
edge of sightglass).
Fill the boiler until the set marking is reached and press button 100% Calibration to
acknowledge.
NRG 16-42 CAN 1...10
1. Click in the menu CAN 1..10 Input in the green input field of the device in question.
2. The display field shows the current values
of the equipment.
3. The menu NRG 16-42 CAN 1..10 is pass-
word protected. Press and enter your
password.
4. To show the setup menu click button .
NRG 26-40
Calibration
Logo
0%
0
Level
Cali. value
0% Calibration
100 %
NRG 16-42
CAN 1...10
Logo
0
Name
0 %
OffNode ID
Electrode online
Temp.interminalboxOK
Reading
Node
0.5 µSSense