Controller Menu – continued
Intermittent blowdown
1. Press button in the menu Controller.
2. The menu Intermittent blowdown is
password protected. Press button and
enter your password.
3. The yellow input fields Remain. run time
show the currently remaining run times.
Once the break time has elapsed, the
pulse time is started and the intermittent
blowdown valve is motored in the required
position for the adjusted break duration.
4. To set the times press button .
5. When the button Manual (pulse) is
pressed, the intermittent blowdown valve is opened for the adjusted pulse duration.
After that the break time starts again with the parameterised break time.
Intermittent blowdown setup
1. In the menu Intermittent blowdown press button .
2. The green input field Signal assignment
shows the name of the signal output to be
activated. Click in the bottom green input
field to show all established signals.
3. Select the digital output that shall be acti-
vated. You will find more information on
equipment setup in the menu Digital Out-
puts.
4. You can enter data in the input fields
Pulse duration (recommended 2 sec.)
and Break duration. For this purpose
click in the green input field.
5. The current value appears in the input mask. Use the on-screen keyboard to over-
write or modify the value.
Intermittent
blowdown
Logo
Valve status
Manual
Remain. run
time/
Remain. run
time/
sec.
hour
00
00:00:00
Open
Intermittent
blowdown setup
Logo
Signal assignment
Pulse duration
Break duration
sec.
hour
00
00
NC