
34
Menus of Inputs/Outputs – continued –
LRG 16-40 calibration - continued -
Select standard curve
1. Click in the green input field of the menu LRG 16-40 Calibration
2. Select in the menu Select standard curve the
corresponding standard temperature curve. The
curves are applicable for various feedwater condi-
tioning agents with different basic conductivities.
For more information refer to the installation man-
ual of the equipment.
Select temperature coefficient
1. Click in the green input field of the menu LRG 16-40 Calibration
2. Select in the menu Select temperature coef-
ficient the corresponding gradient.
Note
With increasing pressure and temperature the conductivity is no longer a
linear function. Choose a suitable temperature compensation method.
Select standard curve
NaHO+H2O 260µS
NaHO+H2O 1080µS
NaHO+H2O 5400µS
NaHO+H2O 11200µS
Na3PO4+H2O 190µS
Na3PO4+H2O 1100µS
Select temp. coefficient
0
1.6 % / °C
1.7 % / °C
....
2.9 % / °C
3.0 % / °C
Comentarios a estos manuales