14
Wiring
– continued –
Wiring diagram for control unit NRS 1-40.1
When using the control unit NRS 1-40.1 for more than two limiting functions the CAN bus
must be supplied with 24V DC by a safety power supply unit (e. g. Siemens SITOP Power 05).
The power supply unit must be in accordance with DIN VDE 0106 (safety separation) and
fused with an overcurrent protective device to EN 61010-1 / VDE 0411.
The CAN bus supply must not be connected to terminals 1 and 5.
2716 17 18 19 20 21 22 23 24 25 26 28 29 30
123456789101112131415
LNN
1
LH
+
-C CS
Terminating resistor
120Ω
Fig. 5
S
Wire link with same potential
Safety circuit / supply
Safety circuit - uninterrupted -
LN
MIN
L
N
Further equipment in
the safety circuit
Attention:
NRS 1-40.1 is the
first device in the
safety circuit.
Do not connect termi-
nals 26, 27, 28, 30.
24V DC
Twisted pair cables
Photo-MOS output
24V-230V AC/DC, 100mA
Instantaneous alarm signal
Timed malfunction signal
CAN bus
Twisted pair cables
NL
GESTRA
NRS 1-40
GESTRA
NRS 1-40.1
Attention