Malfunctions
Fault finding list for level electrode NRG 1.-40 / control unit NRS 1-40.1
Water level below switchpoint "Low water (LW)" - no low level alarm
Fault:
LED "Power" and LEDs 1 - 4 are not illuminated.
Remedy:
Apply mains voltage, wire equipment in accordance with wiring diagram.
Fault:
The electrode rod(s) is/are too long.
Remedy:
Cut electrode rod(s) to the length dictated by the switchpoint LW.
Fault:
If the electrode is installed inside the boiler: The vent hole in the protection tube does not exist
or is obstructed.
Remedy:
Check installation of level electrode. Make sure that the level in the protection tube corre-
sponds to the actual water level.
Water level not yet below switchpoint "Low water (LW)" - but a low level alarm is raised
Fault:
The electrode rod(s) is/are too short.
Remedy:
Replace electrode rod(s) and cut electrode rod(s) to the length dictated by the switchpoint LW.
Fault:
The earth connection to the vessel is interrupted.
Remedy:
Clean seating surfaces and screw in the electrode together with the supplied joint ring
27x32 DIN 7603. Do not insulate the electrode with hemp or PTFE tape!
Fault:
The insulation of the level electrode is faulty.
Remedy:
Replace level electrode.