MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
20
3.2.2 Field Device Status
The Field Device Status is contained in the second data byte in a Slave-to-Master frame as a bit field table. It indicates
the current operating status of the field device as a whole and is not associated with the completion of any command.
Table 3.3 – Field Device Status
Bit Mask Description
0x01 Primary Variable Out of Limits – The PV is beyond its operating limit.
0x02 Non-Primary Variable Out of Limits – A device variable not mapped to PV is beyond its operating limits.
0x04
Loop Current Saturated – The loop current has reached its upper (or lower) endpoint limit and cannot increase (or
decrease) any further.
0x08 Loop Current Fixed – The loop current is being held at a fixed value and is not responding to process variations.
0x10 More Status Available – More status information is available via Command 48, Read Additional Status Information.
0x20 Cold Start – A power failure or Device Reset has occurred.
0x40 Configuration Changed – An operation was performed that changed the device’s configuration.
0x80 Device Malfunction – The device detected a serious error or a failure that compromises device operation.
3.3 Dynamic Variables
The Limitorque HART actuator device supports the following Dynamic Variables:
Table 3.4 – Supported Dynamic Variables
Variable Code Variable Direction Physical Interface
0 PV (Primary Variable) input Analog current input – Analog Channel 0
1 SV (Secondary Variable) output None
2 TV (Tertiary Variable) output None
4 QV (Quaternary Variable) output None
3.4 Device Variables
3.4.1 Supported Device Variables
The Limitorque HART actuator device supports the following Device Variables:
Table 3.5 – Supported Device Variables
Variable
Code
Variable Direction Unit Code
Device Variable
Classification
Device Variable
Family
Range
0 Position setpoint input % (57) Not Classified (0) Valve/Actuator (6) 0-100
1 Current position output % (57) Not Classified (0) Not Used (250) 0-100
2 Torque output % (57) Not Classified (0) Not Used (250) 0-100
3 Motor temperature output °C (32), °F (33) Temperature (64) Not Used (250) Not Limited
4
Compartment
temperature
output °C (32), °F (33) Temperature (64) Not Used (250) Not Limited