MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
flowserve.com
Command 48 can also be used to clear the “More Status Available”. When the device receives command 48 it
compares the Request Data Bytes to the current value; if there is an exact match it clears the “More Status Available
bit corresponding to the requesting device (Primary Master, Secondary Master, Gateway, etc.). If there is not an exact
match or too few bytes are received then the More Status Available bit remains unchanged. Extra Bytes beyond those
supported by the device are ignored.
Table 3.8 HART Defined Status Bits
Extended Device Status (Common Table 17) Supported
Bit Description
0 Maintenance Required Yes
1 Device Variable Alert No
2 Critical Power Failure No
3 Failure No
4 Out of Specification No
5 Function Check No
6 -
7 -
Standardized Status 0 (Common Table 29) Supported
Bit Description
0 Device Variable Simulation Active No
1 Non-Volatile Memory Defect Yes
2 Volatile Memory Defect No
3 Watchdog Reset Executed Yes
4 Power Supply Conditions Out of Range No
5 Environmental Conditions Out of Range No
6 Electronic Defect No
7 Device Configuration Locked Yes
Analog Channel Saturated (Common Table 27) Supported
Bit Description
0 Analog Channel 1 Yes
1 Analog Channel 2 No
2 Analog Channel 3 No
3 Analog Channel 4 No
4 -
5 -
6 -
7 -
Analog Channel Fixed (Common Table 28) Supported
Bit Description
0 Analog Channel 1 Yes
1 Analog Channel 2 No
2 Analog Channel 3 No
3 Analog Channel 4 No
4 -
5 -
6 -
7 -