Flowserve MX HART Field Unit Manual de usuario Pagina 46

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 72
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 45
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
46
Set the Analog Input Loop Current to the high reference value (typically 20 mA, but can be set between 12-28 mA)
and then click OK.
Enter the measured value of the loop current in mA that was applied in the previous step.
A verification of the reference values that were set will be displayed. Click OK to complete the calibration.
Vista de pagina 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 ... 71 72

Comentarios a estos manuales

Sin comentarios