45
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
flowserve.com
Set the Analog Input Loop Current to the low reference value (typically 4 mA, but can be set between 2-7 mA)
and then click OK.
Enter the measured value of the loop current in mA that was applied in the previous step.