Integer
Register
Attribute Description Notes
40036 RW Atmospheric pressure unit selection. 40 = psig
41 = psia
42 = kPa g
43 = kPa a
44 = kg/sq cm g
45 = kg/sq cm a
46 = bar g
47 = bar a
40037 RW Mode source selector. 0 = Digital
1 = Discrete
2 = Remote
40038 RW Operating mode selector. 0 = Calibration mode
1 = Manual mode
2 = Automatic mode
40039 RW Process variable selector. 1 = Liquid flow
2 = Upstream (P
1
) pressure
3 = Downstream (P
2
) pressure
4 = Delta pressure
5 = Temperature
6 = Gas flow
7 = Auxiliary 4-20 mA input
40040 RW Controller action selector. 0 = Reverse acting
1 = Direct acting
40041 RW Setpoint source selector. 0 = 4-20 mA input
1 = Digital
2 = Remote
40042 RW Air action selector. 0 = Air-to-open
1 = Air-to-close
40043 RW 4-20 mA output selector. 0 = Position
1 = Liquid flow
2 = Upstream (P
1
) pressure
3 = Downstream (P
2
) pressure
4 = Delta pressure
5 = Temperature
6 = Gas flow
7 = Auxiliary 4-20 mA input
40044 RW Proportional band for controller. Range 1 to 9999. Percent
40045 RW Derivative time for controller. Range 0 to 9999. Minutes
40046 RW Controller integral reset. Range 0 to 9999. Repeats/minute
StarPac II User Interface Manual 32
Comentarios a estos manuales