Attribute Description
Notes
70299 RW Gas flow in selected units used to output
20 mA on analog output channel.
Range .1 to 1.0E9.
70301 RW Gas flow in selected units used to output
4 mA on analog output channel.
Range 0 to 1.0E9.
70303 RW P
1
process pressure (P1ISA) in selected
units used to output 20 mA on analog
output channel.
Range .1 to 1.0E9.
70305 RW P
1
process pressure (P1ISA) in selected
units used to output 4 mA on analog
output channel.
Range 0 to 1.0E9.
70307 RW P
2
process pressure (P1ISA) in selected
units used to output 20 mA on analog
output channel.
Range .1 to 1.0E9.
70309 RW P
2
process pressure (P1ISA) in selected
units used to output 4 mA on analog
output channel.
Range 0 to 1.0E9.
70311 RW Process temperature in selected units
used to output 20 mA on analog output
channel.
Range -500 to 5000.
70313 RW Process temperature in selected units
used to output 4 mA on analog output
channel.
Range -500 to 5000.
70315 RW Calculated calibration slope for bottom
actuator transducer.
Range -1.0E9 to 1.0E9
70317 RW Calculated calibration slope for top
actuator transducer.
Range -1.0E9 to 1.0E9
70319 RW Calculated calibration slope for 4-20 mA
command input channel.
Range -1.0E9 to 1.0E9
70321 RW Loss of 4-20 mA command signal ramp
rate.
Range -1.0E6 to 1.0E6. Ramp rate is
percent/minute. Set negative to ramp
closed or positive to ramp open on loss of
analog command input.
70323 RW Setpoint deviation range. Range .1 to 100. Device will set alarm
status bit (Setpoint deviation) when
setpoint is this far out of range.
70325 RW Setpoint change percentage over one
second.
Range .1 to 100. Device will set alarm
status bit (Setpoint deviation) when the
indicated process percentage does not
follow the setpoint percentage in one
second.
70327 RW Amount of supply pressure that will be
considered as loss of air supply.
Range 0 to 200. If air supply goes below
this point, the device will set the alarm
status bit (Trip condition).
70329 RW Antoine A fluid coefficient. Range -1000 to 1000. Used to calculate
the fluid vapor pressure.
StarPac II User Interface Manual
41