Integer
Register
Attribute Description Notes
40064 RW Maximum ADC value corresponding to
185 °F ambient temperature.
Range -32768 to 32768
40065 RW Minimum ADC value corresponding to
4 mA on the auxiliary input channel.
Range 0 to 16384
40066 RW Maximum ADC value corresponding to
20 mA on the auxiliary input channel.
Range 0 to 16384
40067 RW Output from analog output channel. Range 0 to 65535. If system is not in
Calibration mode, writing to this register
will not have an effect.
40068 RW Minimum DAC value corresponding to
4 mA on analog output channel.
Range 0 to 65535.
40069 RW Maximum DAC value corresponding to
20 mA on analog output channel.
Range 0 to 65535.
40070 RW Minimum ADC value corresponding to
0 psig process pressure on upstream
pressure (P
1
) transducer.
Range -32768 to 32768
40071 RW Maximum ADC value corresponding to
maximum psig process pressure on
upstream pressure (P
1
) transducer.
Range -32768 to 32768
40072 RW Minimum ADC value corresponding to
0 psig process pressure on downstream
pressure (P
2
) transducer.
Range -32768 to 32768
40073 RW Maximum ADC value corresponding to
maximum psig process pressure on
downstream pressure (P
2
) transducer.
Range -32768 to 32768
40074 RW Minimum ADC value corresponding to
0% open from position Hallpot output.
Range -32768 to 32768
40075 RW Maximum ADC value corresponding to
100% open from position Hallpot output.
Range -32768 to 32768
40076 RW Minimum ADC value corresponding to
calibrated minimum temperature in °F.
Range 0 to 16384.
40077 RW Maximum ADC value corresponding to
calibrated maximum temperature in °F.
Range 0 to 16384.
40078 RW Totalizer reset flag. Range 0 to 1. Writing a value of 1 to this
register causes the device to reset the
totalized flow and time.
40079 RW Read real-time clock flag. Range 0 to 1. Writing a value of 1 to this
register causes the device to load the real-
time clock information into real-time string.
(Register No. 50625)
40080 RW Set real-time clock flag. Range 0 to 1. Writing a value of 1 to this
register causes the device to set the real-
time clock from the real-time string.
(Register No. 50625)
StarPac II User Interface Manual 34