Floating
Point
Register
Attribute Description
Notes
70253 RO Output from position Hallpot in percent.
70255 RO 4-20 mA analog auxiliary signal input
percentage.
70257 RO Setpoint to controller in selected units.
70259 RO Selected process variable value in
selected units.
70261 RW Measured mechanical stroke of valve. Range 1.0E-3 to 100
70263 RW Softlimit maximum percentage. Range -20 to 120. System will not open
past this percentage.
70265 RW Softlimit minimum percentage. Range -20 to 120. System will not close
past this percentage.
70267 RW Full scale auxiliary input percentage. Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.
70269 RW Full scale delta pressure (DPISA) in
selected units.
Range .1 to 1.0E9.. Value is used to
calculate the process variable percentage.
70271 RW Full scale liquid flow in selected units. Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.
70273 RW Full scale gas flow in selected units. Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.
70275 RW Full scale upstream pressure (P1ISA) in
selected units.
Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.
70277 RW Full scale downstream pressure (P2ISA)
in selected units.
Range .1 to 1.0E9. Value is used to
calculate the process variable percentage.
70279 RW Full scale process temperature in
selected units.
Range -500 to 5000. Value is used to
calculate the process variable percentage.
70281 RW Process temperature in selected units
equal to 0% of process.
Range -500 to 5000. Value is used to
calculate the process variable percentage.
70283 RW Percentage of position used to output
20 mA on analog output channel.
Range .1 to 1.0E3.
70285 RW Percentage of position used to output
4 mA on analog output channel.
Range -20 to 120.
70287 RW Percentage of auxiliary input used to
output 20 mA on analog output channel.
Range .1 to 1.0E3.
70289 RW Percentage of auxiliary input used to
output 4 mA on analog output channel.
Range -20 to 120.
70291 RW Delta P (DPISA) in selected units used to
output 20 mA on analog output channel.
Range .1 to 1.0E9.
70293 RW Delta P (DPISA) in selected units used to
output 4 mA on analog output channel.
Range 0 to 1.0E9.
70295 RW Liquid flow in selected units used to
output 20 mA on analog output channel.
Range .1 to 1.0E9.
70297 RW Liquid flow in selected units used to
output 4 mA on analog output channel.
Range 0 to 1.0E9.
StarPac II User Interface Manual 40