Flowserve StarPac II Control Valves Manual de usuario Pagina 43

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 62
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 42
Integer
Register
Attribute Description Notes
40105 RW Variable number of output No. 10 to be
displayed on Local display.
Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.
30106 RO Hardware status register. Bit field Bit Meaning
0 Watch dog reset occurred
1 SRAM R/W failure
2 EPROM checksum error
3 NVRAM R/W failure
4 Thermocouple alarm
5 A-D converter No. 1 failure
6 A-D converter No. 2 failure
7 PII failure
8 Vcc supply failure
9 -15V supply failure
10 +.33V reference failure
11 +15V supply failure
12 D-A converter No. 1 failure
13 +10V reference failure
14 NVRAM checksum error
30107 RO Sensor status register. Bit field Bit Meaning
0 = P
1
sensor error
1 = P
2
sensor error
2 = Top actuator sensor error
3 = Bottom actuator sensor error
4 = Thermocouple sensor error
5 = Ambient temperature sensor error
6 = Position sensor error
40108 RW Loss of supply pressure hold time. Range 0 to 9999. Seconds
30109 RO Process Variable unit type Range 0 to 70
30110 RO Override status
40111 RW Remote command refresh rate Range 0 to 30000 sec
40112 RW Enable mask for alarm source bit fields Range 0 to 255, See register 30028, use
BCD
40113 RW Pressure transducer type 0 = voltage
1 = current
40114 RW Var number for dP valve input to be used
in flow calculation.
-1 to 1023