Floating
Point
Register
Attribute Description
Notes
70495 RW Step time value in seconds. Range 1 to 20. Valve will move to the
stopping position immediately. The device
will collect data for the indicated amount of
time.
70497 RW Signature starting point in percent. Range -10 to 110.
70499 RW Signature stopping point in percent. Range -10 to 110.
70501 RO Signature time data. This value is loaded from device when the
load signature data flag is set to 1.
(Register No. 40084)
70503 RO Signature/Logger top actuator data in
psig.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70505 RO Signature/Logger bottom actuator data in
psig.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70507 RO Signature/Logger I/P input data in
percent.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70509 RO Signature/Logger position Hallpot output
data in percent.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70511 RO Signature/Logger process temperature
data in selected units.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70513 RO Signature/Logger upstream pressure
(P1ISA) data in selected units.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70515 RO Signature/Logger downstream pressure
(P2ISA) data in selected units.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70517 RO Signature/Logger liquid flow data in
selected units.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
70519 RO Signature/Logger gas flow data in
selected units.
This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)
StarPac II User Interface Manual
45